Panasonic Aquarea T-CAP R32 fault H64
Outdoor high pressure abnormality
Heat pumpWhat it means
During operation of cooling and heating, when the outdoor high pressure sensor output signal is 0 Vdc or 5 Vdc.
Likely causes
- Abnormal high voltage detection (5V) at pressure sensor
- Open circuit detection (0V) at pressure sensor
- Faulty high pressure sensor or wiring
- Actual high refrigerant pressure condition
- Excess insertion of refrigerant
- Dirty condenser, attachment of impurity
- Lack of refrigerant gas
Where to start
- If connector normal, check the continuity of the outdoor unit PCB (main) high pressure sensor connector CN-HPS: plug out connector from the outdoor unit PCB (main), measure the continuity pin 1 & 3 (GND) and pin 1 & 4 (5V) of CN-HPS.
- Check high pressure sensor output voltage
- If No continuity, reconnect the high pressure sensor connector to the outdoor unit PCB (main). Turn ON the power and run the system. Measure the DC voltage pin 1 & 3 (GND) of CN-HPS.
The full answer, free
- 2 more checks in order
- How to put it right, step by step
- The manual page for this fault (page 179), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.
Other Panasonic Aquarea T-CAP R32 fault codes
- F12Outdoor high pressure switch activate
- F15Outdoor fan motor (DC motor) mechanism locked
- F16Input over current detection
- F20Compressor overheating
- F22IPM overheating
- F23Output over current detection
- F24Refrigeration cycle abnormality
- F25Four way valve abnormality
- F30Indoor water outlet temperature sensor 2 abnormality
- F36Outdoor air temperature sensor abnormality
- F37Indoor water inlet temperature sensor abnormality
- F40Outdoor discharge pipe temperature sensor abnormality
- F41Power factor correction (PFC) abnormality
- F42Outdoor pipe temperature sensor abnormality
- F43Outdoor defrost temperature sensor abnormality
- F45Indoor water outlet temperature sensor abnormality
- F46Outdoor current transformer open circuit
- H12Connection capability rank abnormality
- H15Compressor tank temperature sensor abnormality
- H20Water pump abnormality
- H23Indoor refrigerant liquid temperature sensor abnormality
- H27Service valve error
- H28Abnormal solar sensor
- H31Abnormal swimming pool sensor