Panasonic Aquarea T-CAP R32 fault F20
Compressor overheating
Heat pumpWhat it means
During operation of cooling and heating, when temperature above 117°C is detected by the outdoor discharge pipe temperature sensor.
Likely causes
- Compressor tank temperature exceeding 107°C
- Excessive compressor load or insufficient cooling of compressor
- Refrigerant circuit fault causing high discharge/tank temperature
- Faulty outdoor discharge pipe temperature sensor
- 2/3 way valve closed
- Refrigerant shortage (refrigerant leakage)
- Clogged expansion valve or strainer
- Faulty outdoor unit PCB (main)
- Faulty compressor
- Inefficient compressor (worn or faulty compression)
- Insufficient refrigerant
- Water leakage or insufficient water flow rate in the system
- Excessive amount of refrigerant
- Excess insertion of refrigerant
- Heat releasing obstruction
- Dirty condenser, attachment of impurity
- Compressor malfunction
- Clogged capillary, expansion valve malfunction
- Clog by moisture
- Lack of refrigerant gas
- Mixture of air (insufficient evacuation)
- Mixture of moisture
- Mixing of unregulated/incompatible compressor oil between R410A and R32 systems
- Energy or electric current limitation requiring high power device shutdown
- Removing refrigerant pipes while compressor is running and valve is open
Where to start
- Measure compressor tank temperature and compare against control bands to determine expected compressor behaviour
- Check compressor frequency reduction behaviour against temperature thresholds (90°C, 96°C/97°C, 113°C/115°C, 117°C)
- Count number of overheat stop occurrences within 30 minutes
The full answer, free
- 53 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 197), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.
Other Panasonic Aquarea T-CAP R32 fault codes
- F15Outdoor fan motor (DC motor) mechanism locked
- F16Input over current detection
- F22IPM overheating
- F23Output over current detection
- F24Refrigeration cycle abnormality
- F25Four way valve abnormality
- F30Indoor water outlet temperature sensor 2 abnormality
- F36Outdoor air temperature sensor abnormality
- F37Indoor water inlet temperature sensor abnormality
- F40Outdoor discharge pipe temperature sensor abnormality
- F41Power factor correction (PFC) abnormality
- F42Outdoor pipe temperature sensor abnormality
- F43Outdoor defrost temperature sensor abnormality
- F45Indoor water outlet temperature sensor abnormality
- F46Outdoor current transformer open circuit