Panasonic Aquarea T-CAP R32 fault F24
Refrigeration cycle abnormality
Heat pumpWhat it means
Detected during operation running (heating/cooling) for more than 5 minutes (excluding deice, pumpdown and test mode) when: water outlet and water inlet temperature difference is less than 1°C; high pressure < 1.90MPa (275 Psi) for more than 10 minutes or < 1.6MPa (232 Psi) for more than 4 minutes; or discharge temperature minus saturation temperature of high pressure is ≥ 60°C.
Likely causes
- Insufficient refrigerant
- Refrigerant shortage (refrigerant leakage)
- Faulty indoor water inlet, indoor water outlet, compressor discharge temp sensor or high pressure sensor
- Excess insertion of refrigerant
- Dirty condenser, attachment of impurity
- Lack of refrigerant gas
Where to start
- Check refrigerant charge
- If sensor conforms, check the pressure sensor value against actual reading
- If pressure sensor value and actual mismatched, replace the pressure sensor
The full answer, free
- 5 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 200), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.
Other Panasonic Aquarea T-CAP R32 fault codes
- F15Outdoor fan motor (DC motor) mechanism locked
- F16Input over current detection
- F20Compressor overheating
- F22IPM overheating
- F23Output over current detection
- F25Four way valve abnormality
- F30Indoor water outlet temperature sensor 2 abnormality
- F36Outdoor air temperature sensor abnormality
- F37Indoor water inlet temperature sensor abnormality
- F40Outdoor discharge pipe temperature sensor abnormality
- F41Power factor correction (PFC) abnormality
- F42Outdoor pipe temperature sensor abnormality
- F43Outdoor defrost temperature sensor abnormality
- F45Indoor water outlet temperature sensor abnormality
- F46Outdoor current transformer open circuit