Panasonic Aquarea T-CAP R32 fault H62
Water flow switch abnormality
Heat pumpWhat it means
During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to determine water flow error.
Likely causes
- Heat pump error triggering backup heat source requirement
- Low water flow rate in the system
- Water pump malfunction
- Air trapped in water circuit
- Faulty water pump
- Faulty water flow switch
- Heat pump error during normal operation triggers automatic switch to force mode
- Flow switch fault or no flow detected
- Vacuum pump oil backflow into charge hoses without proper prevention
- Removing refrigerant pipes while compressor is running and valve is open
Where to start
- If pump working, check the system water passage: is there any water leakage? If Yes, fix the system water leakage.
- If connector normal, check the indoor water flow switch: plug out connector from the indoor unit PCB (main), dismantle the water flow switch, position the water flow switch in reverse direction (downward), measure the continuity of the water flow switch.
- Verify water pump turns ON immediately upon indoor unit ON request
The full answer, free
- 56 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 178), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.
Other Panasonic Aquarea T-CAP R32 fault codes
- F12Outdoor high pressure switch activate
- F15Outdoor fan motor (DC motor) mechanism locked
- F16Input over current detection
- F20Compressor overheating
- F22IPM overheating
- F23Output over current detection
- F24Refrigeration cycle abnormality
- F25Four way valve abnormality
- F30Indoor water outlet temperature sensor 2 abnormality
- F36Outdoor air temperature sensor abnormality
- F37Indoor water inlet temperature sensor abnormality
- F40Outdoor discharge pipe temperature sensor abnormality
- F41Power factor correction (PFC) abnormality
- F42Outdoor pipe temperature sensor abnormality
- F43Outdoor defrost temperature sensor abnormality
- F45Indoor water outlet temperature sensor abnormality
- F46Outdoor current transformer open circuit
- H12Connection capability rank abnormality
- H15Compressor tank temperature sensor abnormality
- H20Water pump abnormality
- H23Indoor refrigerant liquid temperature sensor abnormality
- H27Service valve error
- H28Abnormal solar sensor
- H31Abnormal swimming pool sensor