Panasonic Aquarea T-CAP R32 fault H42

Compressor low pressure protection

Heat pump

What it means

During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -37°C or above 26°C is detected by the outdoor pipe temperature sensor.

Likely causes

  1. Clogged expansion valve or strainer
  2. Insufficient refrigerant
  3. Refrigerant shortage (refrigerant leakage)

Where to start

  1. Check expansion valve/strainer for blockage
  2. Check refrigerant charge
  3. If fan motor normal, check for gas leakage. Is the oil oozing out from the 2/3 way valve? If Yes, repair the pipe flare or union nuts, reclaim and recharge refrigerant.

The full answer, free

  • 3 more checks in order
  • How to put it right, step by step
  • The manual page for this fault (page 175), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.