Panasonic Aquarea T-CAP R32 fault H27

Service valve error

Heat pump

What it means

During cooling operation, this error is triggered when: [a] Indoor refrigerant pipe temperature at compressor startup minus present indoor refrigerant pipe temperature is less than 3°C, AND [b] Present high pressure minus high pressure at compressor startup is less than 3kg/cm2. Judgment only applies for first time cooling operation and not during pump down operation.

Likely causes

  1. High pressure sensor defective or disconnected
  2. Faulty high pressure sensor
  3. Faulty indoor refrigerant pipe temperature sensor
  4. Excess insertion of refrigerant
  5. Dirty condenser, attachment of impurity
  6. Lack of refrigerant gas

Where to start

  1. Check high pressure sensor wiring and continuity
  2. If 3 way valve is not closed, check for clogged expansion valve or strainer (ice formed). If clogged: replace the expansion valve and/or strainer, and reclaim and recharge refrigerant.
  3. If expansion valve/strainer not clogged, check the indoor refrigerant pipe temperature sensor against the sensor characteristic chart. If it does not conform: replace the indoor refrigerant pipe temperature sensor.

The full answer, free

  • 4 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 170), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.