ECA Proteus fault E33

Return water temperature sensor fault

Gas boiler
Free account: the manual page (page 31). No card needed.See the full E33 answer

What it means

Fault indicating a problem with the central heating (CH) return water temperature sensor circuit, including cable connection issues or sensor degradation.

Likely causes

  1. Damaged or improperly connected CH return water temperature sensor cables
  2. Rusting, corrosion or deformation at sensor contact point with copper pipe
  3. Sensor resistance out of tolerance
  4. Main board fault

Where to start

  1. Check whether cable connections are proper and without damage. If not, replace CH return water temperature cables
  2. Check whether there is any rusting, corrosion or deformation inside where it touches the copper pipe, or check whether resistance of sensor is within tolerance; if NO (no rusting/corrosion/deformation, resistance within tolerance), replace the main board
  3. (rusting/corrosion/deformation present or resistance out of tolerance), replace CH return temperature sensor and press 'reset' button

The full answer, free

  • How to put it right, step by step
  • The manual page for this fault (page 31), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

Full E33 fix, readings and manual page. Free.See the full answer

From the ECA manual for the Proteus. Check the model on the data plate before you order parts.