ECA Proteus fault E09
No feedback from gas valve
Gas boilerFree account: 11 more checks, the readings and the manual page (page 28). No card needed.See the full E09 answer
What it means
The main board is not receiving a proper feedback signal from the gas valve, indicating a possible fault in the gas valve, its cabling, or the main board driving circuit.
Likely causes
- Gas valve may be broken
- Gas valve cable connections improper or damaged
- Faulty gas valve cable groups
- Main board fault
Where to start
- Shut down the power of the boiler. Measure the resistance between connecting pins of gas valve. Check whether it is in the range of 110-120 Ohm. If NO, replace the gas valve.
- If resistance is in range (YES), check whether gas valve cable connections are proper and without damage. If NO, replace the gas valve cable groups.
- If cable connections are proper (YES), dismount the gas valve connector. Connect the power to the boiler. Check whether the resistance at the connector ends coming from the circuit board is in the range of 23-25 V when the boiler is trying to ignite. If NO, replace the main board.
The full answer, free
- 11 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 28), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full E09 fix, readings and manual page. Free.See the full answer
From the ECA manual for the Proteus. Check the model on the data plate before you order parts.
Other ECA Proteus fault codes
- E01Ignition/ionization electrode fault
- E02Relevant to main board and gas valve faults
- E033 way shaft group / motorized valve related fault
- E05Fan feedback fault
- E08Relevant to main board and gas valve faults
- E12Relevant to main board and gas valve faults
- E15Temperature sensors measurement deviation fault
- E16Related to plate heat exchanger / pump fault
- E17Related to plate heat exchanger / pump fault
- E18Immersion/flue gas NTC related fault
- E21Relevant to main board and gas valve faults
- E33Return water temperature sensor fault
- E35Supply water temperature sensor fault
- E82Ignition/ionization electrode fault
- F073 way shaft group / motorized valve related fault
- F13Over-resetting fault
- F25Relevant to main board fault
- F39Outdoor sensor fault
- F47Water pressure sensor fault
- F50Storage tank sensor fault
- F51PT1000 solar sensor fault
- F52Immersion type NTC fault
- F53Flue gas sensor fault
- F58Relevant to main heat exchanger fault