LG Therma V fault 29
Comp over current
Heat pumpWhat it means
Input current for Inverter Compressor exceeds the limit.
Likely causes
- Inverter compressor input current exceeds limit
- Insufficient power-on time before operation (less than 12 hours)
- Faulty IPM (Intelligent Power Module)
- Faulty compressor (insulation or coil failure)
- Faulty inverter board
- Unstable or zero output voltage from inverter
- Fan locked
- Obstruction/shield around the heat exchanger
- Insufficient distance between product and wall
- Piping condition issues such as pipe bending
- EEV operation/connection status fault
- Abnormal refrigerant pressure
- Compressor restraint
- Compressor wiring reverse phase loss
- Short circuit or opening of internal connection line in compressor
- Compressor winding resistance out of spec
- Compressor insulation resistance failure
- Inverter PCB assembly or connector connection fault
- IGBTM failure
- Refrigerant accumulation in internal compressor after mounting or extended power-off period, causing temporary reduced insulation resistance
Where to start
- Step 1: Check how long power has been on during operation. If power on for 12 hours or more, go to No.2. If power on for 12 hours or less, apply power for the designated time (12 hours) then go to No.2.
- Step 2: Check if failure appears again when starting operation.
- Step 2a: If the compressor stops and the same error appears again, check if IPM may have failed.
The full answer, free
- 19 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 72), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the LG manual for the Therma V. Check the model on the data plate before you order parts.
Other LG Therma V fault codes
- 03Communication error between indoor unit and wired remote controller
- 05Communication error between main PCB(indoor) and main PCB(outdoor cycle)
- 14Problem in flow rate
- 15Overheating of water pipe
- 232Problem in flow sensor
- 26No position error
- 40Inv comp CT sensor error
- 52Inv PCB(outdoor) - main PCB(outdoor cycle) communication error
- 53Main PCB(indoor) - main PCB(outdoor) communication error
- 57Main PCB(indoor) → inv PCB(outdoor) communication error
- 60Outdoor EEPROM error
- 67Fan lock error
- CH01Room air temperature sensor fault
- CH02Inlet pipe temperature sensor fault
- CH03Bad communication between remote controller and indoor unit
- CH05Bad communication between outdoor unit and indoor unit
- CH08DHW tank temperature sensor fault
- CH09PCB program (EEPROM) fault
- CH114Injection in sensor error
- CH115Injection out sensor error
- CH13DHW tank temperature sensor fault
- CH14Problem in flow rate
- CH15Water pipe strange overheat
- CH16Problems in sensors (heater water temperature sensor error)