Immergas Victrix fault DL

System deaeration procedure

Gas boiler

What it means

Function to correctly perform deaeration of new central heating systems, particularly important for floor/underfloor systems. Cyclically activates the pump and 3-way valve to purge air from the system.

Likely causes

  1. Lack of water in the appliance
  2. Little water circulation in the system
  3. Blocked pump
  4. No gas
  5. Condensate drain clogged
  6. Disconnected PWM signal wire (when boiler is requesting ignition but pump stays in stand-by)
  7. Disconnection of the PWM control signal between PCB and pump
  8. Boiler electronics not requesting pump ignition (normal, condition OK)
  9. Boiler electronics requesting pump ignition but pump not responding (faulty condition, probable disconnection of the PWM signal)
  10. Blocked pump (Par. 1.29)
  11. Wear or degradation of manifold seals over time
  12. Manifold opened for maintenance requiring seal replacement

Where to start

  1. Access special functions as described in Paragraph 3.12 and select 'MA' function
  2. Ensure appliance is in stand-by mode (if connected to CARV2, stand-by must be obtained via remote control panel)
  3. Press and hold the INFO button for more than 5 seconds until display shows flashing double dash '--'

The full answer, free

  • 91 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 80), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

From the Immergas manual for the Victrix. Check the model on the data plate before you order parts.

Other Immergas Victrix fault codes