Ideal Logic Air fault 33
Flow thermistor (indoor) fault
Heat pumpFree account: 2 more checks, the readings and the manual page (page 57). No card needed.See the full 33 answer
What it means
The controller has detected a fault on the indoor flow thermistor circuit. The manual's fault-finding chart (page 70) checks the wiring, then the indoor flow thermistor by resistance, then the RVS21 PCB.
Likely causes
- Loose or disconnected wiring between the control box flow thermistor connections and the indoor flow thermistor.
- Faulty Indoor Flow Thermistor (resistance out of range).
- Faulty RVS21 PCB.
Where to start
- Read the fault history to confirm the code and when it occurred: Settings, user level Installer (password), Test function menu, Fault History (6800 History 1, 6801 Fault Code 1), page
- The last 10 faults can be scrolled through.
- Check the wiring between the control box flow thermistor connections and the indoor flow thermistor is securely connected at both ends.
The full answer, free
- 2 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 57), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full 33 fix, readings and manual page. Free.See the full answer
From the Ideal manual for the Logic Air. Check the model on the data plate before you order parts.
Other Ideal Logic Air fault codes
- 127Anti-legionella temperature fault
- 366Room temperature sensor fault
- 385Low mains voltage
- 490No outdoor connection
- 499No outdoor connection
- 516No outdoor connection
- 60Room stat 1 fault
- 7Number of heat pump starts exceeded
- 9.1.11LPB (cascade) address collision (controller code 82)
- 9.1.12BSB short circuit (controller code 83)
- 9.1.13BSB address collision (controller code 84)
- 9.1.142 clock time masters (controller code 100)
- 9.1.15Clock without back-up (controller code 102)
- 9.1.16Source temperature too low
- 9.1.177093 DHW setpoint fault (controller code 126)
- 9.1.18Anti-legionella temperature fault (controller code 127)
- 9.1.20Configuration fault (controller code 146)
- 9.1.22Room temperature sensor fault (controller code 366)
- 9.1.24Low mains voltage (controller code 385)
- 9.1.25No cascade master (controller code 489)
- 9.1.26No outdoor connection (controller code 490, 499 and 516)
- 9.1.28Number of heat pump starts exceeded (controller code 7)
- 9.1.29No central heating but hot water works