Vaillant Gas boiler fault F.83

Flow and/or return temperature sensor temperature change fault

Gas boiler

What it means

Fault relating to unexpected temperature change detected at the flow and/or return temperature sensors.

Likely causes

  1. Water deficiency in the heating installation
  2. Flow NTC not in contact with the flow pipe
  3. Return NTC not in contact with the return pipe
  4. Defective heating flow or return temperature sensor

Where to start

  1. Check whether the flow NTC is lying against the flow pipe correctly.
  2. Check whether the return NTC is lying against the return pipe correctly.
  3. Pull out the heating flow (4) and return temperature sensor (3)

The full answer, free

  • 1 more check in order
  • How to put it right, step by step
  • The manual page for this fault (page 63), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

From the Vaillant manual for the Gas boiler. Check the model on the data plate before you order parts.