Vaillant Gas boiler fault F.75
Pump fault/water deficiency
Gas boilerWhat it means
A pump malfunction or water deficiency has been detected. Further diagnosis available via diagnostics code D.149.
Likely causes
- Pump blocked
- Electrical pump fault
- Pump dry run
- Pressure sensor fault
- No feedback from the pump
- Incorrect pump detected
- Flow rate at the end of the purge programme is insufficient
- Closed stopcocks in the hydraulic installation
- Closed thermostatic valves on radiators
- Insufficient filling pressure in the heating installation
- Air remaining in the system preventing adequate flow
- Malfunction
- D.149 = 1, pump blocked alarm
- Defective pump
Where to start
- Read parameter D.149 to determine the specific circulation fault value
- Match D.149 value to the corresponding cause from the list: 0=No fault, 1=Pump blocked, 2=Electrical pump fault, 3=Pump dry run, 5=Pressure sensor fault, 6=No feedback from the pump, 7=Incorrect pump detected, 8=Flow rate at end of purge programme insufficient
- Ensure that all of the stopcocks in the hydraulic installation are open
The full answer, free
- 9 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 62), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
From the Vaillant manual for the Gas boiler. Check the model on the data plate before you order parts.
Other Vaillant Gas boiler fault codes
- F.00Flow temperature sensor interruption
- F.01Return temperature sensor interruption
- F.03Cylinder temperature sensor interruption
- F.10Flow temperature sensor short circuit
- F.11Return temperature sensor short circuit
- F.13Cylinder temperature sensor short circuit
- F.22Safety shutdown: water deficiency
- F.23Safety shutdown: temperature spread too great
- F.24Safety shutdown: temperature rise too fast
- F.25Safety shutdown: flue gas temperature too high
- F.27Safety shutdown: flame simulation
- F.32Fan fault
- F.33Air pressure switch fault
- F.64Fault: electronics/NTC
- F.65Electronics temperature fault
- F.72Flow and/or return temperature sensor fault
- F.74Water pressure sensor signal outside correct range (too high)
- F.77Accessory fault (flue non-return flap, condensate pump, etc.)
- F.83Flow and/or return temperature sensor temperature change fault
- F.84Temperature difference fault at the flow and return temperature sensors
- F.85Flow and return temperature sensors installed incorrectly (inverted)
- P.02Minimum load check programme
- S.42Flue non-return flap closed
- S.46Comfort protection: minimum load, loss of flame