Mitsubishi Ecodan fault L5
Flow/return/tank/zone water temperature thermistor failure
Heat pumpWhat it means
Error code displayed when one of THW1, THW2, THW5, THW6, THW7, THW8, or THW9 is at open or short circuit. Open detection at -39ºC or below, short detection at 88.5ºC or above.
Likely causes
- Failed thermistor TH1A, TH2, THW1, THW2, THWB1, THW5, THWB2, TH1B, THW6, THW7, THW8, or THW9
- Connector/terminal wire has become detached or loose wiring
- Thermistor fault
- FTC board failure
- Thermistor on the wireless remote controller or main remote controller may be defective
- Incorrect setting of the DIP switch(es)
Where to start
- Enter request code 567 to identify the specific failed thermistor
- Visually check the terminals and connections and reattach as appropriate
- Check resistance of thermistor against table in section 10-6
The full answer, free
- 3 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 48), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Mitsubishi manual for the Ecodan. Check the model on the data plate before you order parts.
Other Mitsubishi Ecodan fault codes
- 1Main remote controller display is blank
- 10Temperature of DHW tank water dropped
- 12Water leakage
- 13Heating system does not reach the set temperature
- 14In 2-zone temperature control, only Zone2 does not reach the set temperature
- 15When a PUHZ-FRP outdoor unit is connected, DHW or heating operation cannot run
- 16When a PUHZ-FRP outdoor unit is connected and in heat recovery operation, the set...
- 19Water discharges from pressure relief valve (primary circuit)
- 2'please wait' remains displayed on main remote controller
- 20Water discharges from pressure relief valve (sanitary circuit)
- 23Noisy water circulation pump
- 25Mechanical noise heard coming from the cylinder unit
- 26Water circulation pump runs for a short time unexpectedly
- 3Main screen appears then disappears after pressing ON button
- 33L6 error (circulation water freeze protection error) occurs during DHW or LP mode...
- 34The energy monitor value seems not correct
- 4LED2 on FTC is off (FTC powered on independent source)
- 5LED2 on FTC is blinking
- 6LED4 on FTC is off
- 7No water at hot tap
- 8Cold water at tap
- 9Water heating takes longer
- E0Main remote controller communication failure (reception error)
- E1Main remote controller control board failure