Mitsubishi Ecodan fault 34
The energy monitor value seems not correct
Heat pumpWhat it means
Energy monitor values (consumed electric energy and delivered heat energy) appear incorrect, which could result from DIP switch settings, external meter configuration, external meter failure, or FTC board failure. Note: discrepancies can occur between actual and calculated values; connecting power meter(s) and heat meter to FTC board (locally supplied) improves accuracy.
Likely causes
- Incorrect setting of the energy monitor
- Non-connectable type of external meter (local supply) is connected
- External meter (local supply) failure
- FTC board failure
Where to start
- Check if the DIP switch SW3-4 is set correctly for consumed electric energy (electric energy meter local supply)
- Check if DIP switch SW3-8 is set correctly for delivered heat energy (heat meter local supply)
- If external electric energy meter and/or heat meter is not used, check the setting for electric heater and water pump(s) input is correct, referring to Energy monitor setting in section 9-4
The full answer, free
- 11 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 58), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Mitsubishi manual for the Ecodan. Check the model on the data plate before you order parts.
Other Mitsubishi Ecodan fault codes
- 1Main remote controller display is blank
- 10Temperature of DHW tank water dropped
- 12Water leakage
- 13Heating system does not reach the set temperature
- 14In 2-zone temperature control, only Zone2 does not reach the set temperature
- 15When a PUHZ-FRP outdoor unit is connected, DHW or heating operation cannot run
- 16When a PUHZ-FRP outdoor unit is connected and in heat recovery operation, the set...
- 19Water discharges from pressure relief valve (primary circuit)
- 2'please wait' remains displayed on main remote controller
- 20Water discharges from pressure relief valve (sanitary circuit)
- 23Noisy water circulation pump
- 25Mechanical noise heard coming from the cylinder unit
- 26Water circulation pump runs for a short time unexpectedly
- 3Main screen appears then disappears after pressing ON button
- 33L6 error (circulation water freeze protection error) occurs during DHW or LP mode...
- 4LED2 on FTC is off (FTC powered on independent source)
- 5LED2 on FTC is blinking
- 6LED4 on FTC is off
- 7No water at hot tap
- 8Cold water at tap
- 9Water heating takes longer
- E0Main remote controller communication failure (reception error)
- E1Main remote controller control board failure
- E2Main remote controller control board failure