LG Therma V fault CH67
Outdoor fan lock
Heat pumpWhat it means
Fan RPM is 10RPM or less for 5 seconds when ODU fan starts, or 40 RPM or less after fan starting, indicating the outdoor fan is locked or not rotating correctly.
Likely causes
- Bad Motor / Poor assembly.
- Misconnection Fan Motor connector.
- Rotation in reverse direction after speed command.
- Bad Fan Board
- Fan lock by Heavy snow
- Fan locked
- Obstruction/shield around the heat exchanger
- Insufficient distance between product and wall
- Piping condition issues such as pipe bending
- EEV operation/connection status fault
- Abnormal refrigerant pressure
- Compressor restraint
- Compressor wiring reverse phase loss
- Short circuit or opening of internal connection line in compressor
- Compressor winding resistance out of spec
- Compressor insulation resistance failure
- Inverter PCB assembly or connector connection fault
- IGBTM failure
Where to start
- Set tester to resistance mode.
- Measure resistance between U-V, U-W, and V-W terminals of the fan motor.
- Compare measured values against expected 43.1±5% Ω at 25°C standard.
The full answer, free
- 15 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 123), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the LG manual for the Therma V. Check the model on the data plate before you order parts.
Other LG Therma V fault codes
- 03Communication error between indoor unit and wired remote controller
- 05Communication error between main PCB(indoor) and main PCB(outdoor cycle)
- 14Problem in flow rate
- 15Overheating of water pipe
- 232Problem in flow sensor
- 26No position error
- 29Comp over current
- 40Inv comp CT sensor error
- 52Inv PCB(outdoor) - main PCB(outdoor cycle) communication error
- 53Main PCB(indoor) - main PCB(outdoor) communication error
- 57Main PCB(indoor) → inv PCB(outdoor) communication error
- 60Outdoor EEPROM error
- 67Fan lock error
- CH01Room air temperature sensor fault
- CH02Inlet pipe temperature sensor fault
- CH03Bad communication between remote controller and indoor unit
- CH05Bad communication between outdoor unit and indoor unit
- CH08DHW tank temperature sensor fault
- CH09PCB program (EEPROM) fault
- CH114Injection in sensor error
- CH115Injection out sensor error
- CH13DHW tank temperature sensor fault
- CH14Problem in flow rate
- CH15Water pipe strange overheat