LG Therma V fault CH232
Reference table correlating water flow rate (l/min) to expected sensor output voltage...
Heat pumpWhat it means
Reference table correlating water flow rate (l/min) to expected sensor output voltage (V) at the CN_F_SENSOR connector (Blue/4), used to verify sensor operation during CH232 diagnosis.
Likely causes
- Flow sensor is electrically open
- Water pump is in trouble
- Cable interference around the flow sensor causing false switch state detection
- Use of compressed air or oxygen for leak testing
Where to start
- View Current flow rate on the service/display screen to verify actual system water flow rate.
- Step 3: If pressure OK, check water pump still running (vibration test at terminal box, or 'Water Pump Operating' on control panel) - if NO, investigate flow sensor (branch B)
- Step 4: If pump running, check if control panel shows CH14 - if NO, condition is normal (END); if YES, investigate water pump trouble (branch C)
The full answer, free
- 4 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 77), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the LG manual for the Therma V. Check the model on the data plate before you order parts.
Other LG Therma V fault codes
- 03Communication error between indoor unit and wired remote controller
- 05Communication error between main PCB(indoor) and main PCB(outdoor cycle)
- 14Problem in flow rate
- 15Overheating of water pipe
- 232Problem in flow sensor
- 26No position error
- 29Comp over current
- 40Inv comp CT sensor error
- 52Inv PCB(outdoor) - main PCB(outdoor cycle) communication error
- 53Main PCB(indoor) - main PCB(outdoor) communication error
- 57Main PCB(indoor) → inv PCB(outdoor) communication error
- 60Outdoor EEPROM error
- 67Fan lock error
- CH01Room air temperature sensor fault
- CH02Inlet pipe temperature sensor fault
- CH03Bad communication between remote controller and indoor unit
- CH05Bad communication between outdoor unit and indoor unit
- CH08DHW tank temperature sensor fault
- CH09PCB program (EEPROM) fault
- CH114Injection in sensor error
- CH115Injection out sensor error
- CH13DHW tank temperature sensor fault
- CH14Problem in flow rate