ECA ARCEUS fault E03
Overheat thermostat trip
Gas boilerFree account: 44 more checks, the readings and the manual page (page 44). No card needed.See the full E03 answer
What it means
Indicates protection shutdown related to the overheat thermostat, which shuts off the contact in case of overheating in the main exchanger. Can also incorrectly trigger if the thermostat is faulty, preventing the device from heating even without actual overheating.
Likely causes
- Contactor not ensuring device protection in emergency
- Heating circuit not activated due to contactor fault
- Mainboard damage caused by faulty contactor
- Incorrect feedback signal causing error
- Plate exchanger leakage causing water mixing or pressure drop
- Contactor fault preventing proper power circuit control
- Motorised valve cable damaged or not properly mounted on connector
- Incorrect resistance reading between pins
- Valve/pump mechanical position fault
- Relay board failure in last-stage switching
- Relay stuck in transmission causing heating without request
- No water circulation combined with stuck relay causing overheating
- Short-circuit between relay coils causing excessive current draw and mainboard damage
- Pump electrical connection fault
- Pump motor burned out (short-circuit)
- Air purge failure on pump causing pressure loss
- Motorised valve cable damaged or improperly mounted on connector
- Motorised valve position fault (pin not switching between up/down position)
- Overheat thermostat open or short-circuit
- Pump not circulating water (blockage in heating circuit or closed valves)
- Motorised valve not switching correctly between domestic water and central heating
- Broken or damaged feedback cables
- Genuine overheating on the upper surface of the heat exchanger
- Overheat thermostat failing to open contact under overheating (no protection)
- Overheat thermostat incorrectly shutting off contact when surface is not overheated (faulty component)
Where to start
- Make sure cable connections are in accordance with user manual and cables are undamaged, especially on main output contacts
- Turn off power supply, measure resistance between contacts no. 13 and 14 - expect open-circuit or above 100k ohms
- Turn on power supply and put device into heating mode, measure voltage between contacts no. 13 and 14 and neutral terminal - expect 210-240 VAC
The full answer, free
- 44 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 44), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full E03 fix, readings and manual page. Free.See the full answer
From the ECA manual for the ARCEUS. Check the model on the data plate before you order parts.
Other ECA ARCEUS fault codes
- E04Associated with contactor malfunction
- E13Too frequent error reset error
- E80Surface type NTC related fault
- F33Surface type NTC related fault
- F34Low voltage error
- F35Surface type NTC related fault
- F39Outdoor temperature sensor error
- F47Water pressure sensor fault
- F50Solar energy boiler tank temperature sensor error
- F51Solar panel temperature sensor (PT1000) error
- F52Submersion type NTC (DHW outlet temperature sensor) fault