Midea R32 M thermal Arctic Mono fault P4
Discharge temperature protection
Heat pumpWhat it means
Error code 24. Discharge temperature protection detected by user interface and refrigerant system main PCB.
Likely causes
- Discharge temperature exceeds 115°C
- Insufficient refrigerant charge
- Excessive compressor load
- Poor heat rejection at condenser
- Abnormally high discharge temperature, transient temperature spikes High ambient temperature, refrigerant undercharge, expansion valve malfunction, compressor overload
- Dirt/blockage on air side heat exchanger, fan or air outlets
- Dirt/blockage on water side heat exchanger, water piping, circulator pumps or water flow switch
- Excessive discharge temperature
- Refrigerant charge issue
- Compressor fault
- Discharge temperature exceeding 105°C indicating high compressor load or high ambient/system conditions
- Crushed or bent pipe
- Blocked EXV
- Dirty filter
- Compressor current exceeding Currentmax threshold
Where to start
- Measure discharge temperature
- Monitor discharge temperature during operation Check discharge temperature reading, verify refrigerant charge level, inspect expansion valve
- Check compressor operating conditions
The full answer, free
- 44 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 67), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the R32 M thermal Arctic Mono. Check the model on the data plate before you order parts.
Other Midea R32 M thermal Arctic Mono fault codes
- BHPED board checking fail
- C7Transducer module temperature too high protect
- D0Oil return operation in progress
- E0Water flow failure (repeated E8 occurrence)
- E1Phase sequence error
- E2Communication error between outdoor unit and user interface
- E3Backup electric heater water outlet temperature sensor error
- E4Domestic hot water tank temperature sensor error
- E5Air side heat exchanger refrigerant outlet temperature sensor error
- E6Outdoor ambient temperature sensor error
- E7Balance tank sensor Tbt1 error
- E8Water flow failure
- E9Suction pipe temperature sensor error
- EADischarge pipe temperature sensor error
- EBSolar board sensor tsolar error
- ECBalance tank sensor Tbt2 error
- EDWater side heat exchanger water inlet temperature sensor error
- EEHydronic system EEPROM error
- ELCommunication fault between hydraulic module and MH-kit
- F1DC bus voltage is too low
- H0Communication error between refrigerant system main control chip and hydronic system...
- H1Communication error between refrigerant system main control chip and inverter driver chip
- H2Water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor error
- H3Water side heat exchanger refrigerant outlet temperature sensor error