Midea R32 M thermal Arctic Mono fault C7
Transducer module temperature too high protect
Heat pumpWhat it means
Transducer module temperature too high protect (serial number 65)
Likely causes
- Excessive ambient temperature, blocked cooling airflow, transducer module malfunction
- Module temperature at or above Tf2 threshold (model dependent: 75°C for 4-6kW, 81°C for 8-10kW, 100°C for 12-16kW 1ph, 84°C for 12-16kW 3ph)
- Insufficient cooling of module
- Excessive compressor load or ambient conditions
- Module temperature exceeding maximum safe operating temperature
Where to start
- Check transducer module temperature reading, verify ambient conditions, inspect for airflow blockage
- Measure module temperature
- Identify unit model/capacity to determine correct Tf2/Tf0 threshold
The full answer, free
- 2 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 66), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the R32 M thermal Arctic Mono. Check the model on the data plate before you order parts.
Other Midea R32 M thermal Arctic Mono fault codes
- BHPED board checking fail
- D0Oil return operation in progress
- E0Water flow failure (repeated E8 occurrence)
- E1Phase sequence error
- E2Communication error between outdoor unit and user interface
- E3Backup electric heater water outlet temperature sensor error
- E4Domestic hot water tank temperature sensor error
- E5Air side heat exchanger refrigerant outlet temperature sensor error
- E6Outdoor ambient temperature sensor error
- E7Balance tank sensor Tbt1 error
- E8Water flow failure
- E9Suction pipe temperature sensor error
- EADischarge pipe temperature sensor error
- EBSolar board sensor tsolar error
- ECBalance tank sensor Tbt2 error
- EDWater side heat exchanger water inlet temperature sensor error
- EEHydronic system EEPROM error
- ELCommunication fault between hydraulic module and MH-kit
- F1DC bus voltage is too low
- H0Communication error between refrigerant system main control chip and hydronic system...
- H1Communication error between refrigerant system main control chip and inverter driver chip
- H2Water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor error
- H3Water side heat exchanger refrigerant outlet temperature sensor error
- H5Room temperature sensor error