Midea R32 M thermal Arctic Mono fault L0
Inverter module protection
Heat pumpWhat it means
Inverter module protection detected by refrigerant system main PCB. Displayed as P6/H4 on user interface.
Likely causes
- Communication wire not connected properly
- Inverter module damaged
- Voltage between F0 and GND too low
- Inverter module has overheated
- Inverter module over-current
- Inverter module failure
- Outdoor unit ventilation is not good
- Inverter module fault
Where to start
- Measure the resistance between each of U, V and W and each of P and N on the inverter module. All resistances should be infinite. Refer to Figure 4-3.5 to 4-3.7 in Part 4, 3.1
- Measure normal resistances of inverter compressor: 0.7-1.5Ω among U V W and infinite between each of U V W and ground
- Check communication wire between refrigerant system main control board and inverter module (4 pins) for proper connection
The full answer, free
- 25 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 67), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the R32 M thermal Arctic Mono. Check the model on the data plate before you order parts.
Other Midea R32 M thermal Arctic Mono fault codes
- BHPED board checking fail
- C7Transducer module temperature too high protect
- D0Oil return operation in progress
- E0Water flow failure (repeated E8 occurrence)
- E1Phase sequence error
- E2Communication error between outdoor unit and user interface
- E3Backup electric heater water outlet temperature sensor error
- E4Domestic hot water tank temperature sensor error
- E5Air side heat exchanger refrigerant outlet temperature sensor error
- E6Outdoor ambient temperature sensor error
- E7Balance tank sensor Tbt1 error
- E8Water flow failure
- E9Suction pipe temperature sensor error
- EADischarge pipe temperature sensor error
- EBSolar board sensor tsolar error
- ECBalance tank sensor Tbt2 error
- EDWater side heat exchanger water inlet temperature sensor error
- EEHydronic system EEPROM error
- ELCommunication fault between hydraulic module and MH-kit
- F1DC bus voltage is too low
- H0Communication error between refrigerant system main control chip and hydronic system...
- H1Communication error between refrigerant system main control chip and inverter driver chip
- H2Water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor error
- H3Water side heat exchanger refrigerant outlet temperature sensor error