Midea R32 M thermal Arctic Mono fault HA
Water side heat exchanger water outlet temperature sensor error
Heat pumpWhat it means
Error code 49. Water side heat exchanger water outlet temperature sensor (Sensor Tw_out) fault detected by user interface and hydronic system main PCB.
Likely causes
- Temperature sensor not connected properly or has malfunctioned. Damaged hydronic system main PCB.
- Sensor Tw_out circuit fault
- Sensor damage or disconnection
- Main board fuse damaged/blown
- Insufficient refrigerant caused by refrigerant leakage
- Low pressure side blocked by crushed or bent pipe, blocked EXV, or dirty filter
- Poor air side heat exchanger heat exchange in heating or DHW mode
- Insufficient water flow rate in cooling mode
- Outdoor main PCB fault (last resort)
- Inverter module damaged
- Discharge temperature exceeding 105°C indicating high compressor load or high ambient/system conditions
- Crushed or bent pipe
- Blocked EXV
- Dirty filter
- Hydronic box main PCB fault
- Damaged cables between hydronic box main PCB and outdoor unit main PCB
- Outdoor unit main PCB fault
- Incorrect or abnormal input power supply (N or L)
Where to start
- Identify sensor type based on fault code
- Locate corresponding port on refrigerant system main PCB for that model
- Check connection at identified port
The full answer, free
- 72 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 67), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the R32 M thermal Arctic Mono. Check the model on the data plate before you order parts.
Other Midea R32 M thermal Arctic Mono fault codes
- BHPED board checking fail
- C7Transducer module temperature too high protect
- D0Oil return operation in progress
- E0Water flow failure (repeated E8 occurrence)
- E1Phase sequence error
- E2Communication error between outdoor unit and user interface
- E3Backup electric heater water outlet temperature sensor error
- E4Domestic hot water tank temperature sensor error
- E5Air side heat exchanger refrigerant outlet temperature sensor error
- E6Outdoor ambient temperature sensor error
- E7Balance tank sensor Tbt1 error
- E8Water flow failure
- E9Suction pipe temperature sensor error
- EADischarge pipe temperature sensor error
- EBSolar board sensor tsolar error
- ECBalance tank sensor Tbt2 error
- EDWater side heat exchanger water inlet temperature sensor error
- EEHydronic system EEPROM error
- ELCommunication fault between hydraulic module and MH-kit
- F1DC bus voltage is too low
- H0Communication error between refrigerant system main control chip and hydronic system...
- H1Communication error between refrigerant system main control chip and inverter driver chip
- H2Water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor error
- H3Water side heat exchanger refrigerant outlet temperature sensor error