Midea Heat pump fault F1

Protection for DC bus undervoltage

Heat pump

What it means

Protection triggered when the DC bus voltage on a single phase inverter PCB falls to or below 200VDC, indicating undervoltage condition on the inverter bus.

Likely causes

  1. Faulty inverter power module
  2. Faulty three-phase bridge rectifier (3Ph models)
  3. Abnormal state detected requiring compressor protection
  4. Set temperature reached (normal stop)

Where to start

  1. Refer to Part 4 Appendix: Guide for identifying inverter PCB failure to determine PCB status before component replacement
  2. Set multimeter to diode test function (secondary tube available)
  3. For 1Ph models, test inverter circuit test points only

The full answer, free

  • 11 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 144), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Midea manual for the Heat pump. Check the model on the data plate before you order parts.