Worcester Bosch Greenstar i System ErP fault C7214

Fan does not run during start up

Gas boiler
Free account: 1 more check, the readings and the manual page (page 66). No card needed.See the full C7214 answer

What it means

Fan/airflow fault: the fan did not run during the start up phase.

Likely causes

  1. Fan harness or connector fault.
  2. No mains supply to the fan.
  3. Faulty fan.
  4. Control box connection fault or faulty control box.

Where to start

  1. Check the fan harness and connector.
  2. Check for 230 Vac across the brown and blue wires at the fan.
  3. Check fan operation.

The full answer, free

  • 1 more check in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 66), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

Full C7214 fix, readings and manual page. Free.See the full answer

From the Worcester Bosch manual for the Greenstar i System ErP. Check the model on the data plate before you order parts.