Worcester Bosch Greenstar 4000 System fault 227
No flame signal after ignition
Gas boilerFree account: 9 more checks, the readings and the manual page (page 71). No card needed.See the full 227 answer
What it means
Locking fault (V category): no flame signal was detected after ignition. The boiler locks out until reset.
Likely causes
- Damaged ceramic insulator causing the spark to earth.
- No or low gas supply to the property or at the gas valve inlet.
- Low pressure when the gas valve opens.
- Gas valve failing to open because of a voltage problem or a blocked inlet filter.
- Obstruction in the air intake to the fan, giving the wrong CO2 ratio.
- Condensate siphon blocked or restricted, or condensate pipe frozen.
- Flue blocked or restricted.
- Heat exchanger blocked or restricted.
- Damaged burner.
- Failed spark electrode or lead.
- Failed flame sense electrode or lead.
- Poor rectification ground (black wire to the heat exchanger).
Where to start
- Check the ceramic insulator is not damaged: twist and pull to make sure it is not broken.
- Check the gas supply to the property and at the gas valve inlet.
- Check for a drop in pressure when the gas valve opens.
The full answer, free
- 9 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 71), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full 227 fix, readings and manual page. Free.See the full answer
From the Worcester Bosch manual for the Greenstar 4000 System. Check the model on the data plate before you order parts.
Other Worcester Bosch Greenstar 4000 System fault codes
- 1010No communication via EMS BUS connection
- 1021Cylinder charging or hot water temperature sensor faulty
- 1022Cylinder temperature sensor faulty or contact problems
- 1037Outside temperature sensor faulty - heating backup operation active
- 1065System pressure sensor faulty or not connected
- 1068Outside temperature sensor or lambda probe faulty
- 1073Short-circuit at flow temperature sensor
- 1074No signal from flow temperature sensor
- 1075Heat exchanger temperature sensor short circuit
- 1076Heat exchanger temperature sensor disconnected
- 2085Internal fault
- 224Maximal flue gas thermostat or heat exchanger maximal thermostat has activated
- 228Flame signal without flame present
- 233Boiler identification module or device electronics faulty
- 234Gas valve electrical fault
- 238Boiler electronics faulty
- 242Boiler electronics system fault
- 245System fault boiler electronics / basic controller
- 249System fault boiler electronics / basic controller
- 250System fault boiler electronics / basic controller
- 251System fault boiler electronics / basic controller
- 252System fault boiler electronics / basic controller
- 253System fault boiler electronics / basic controller
- 254System fault boiler electronics / basic controller