Samsung EHS fault E507

Comp down due to high pressure or high pressure switch open

Heat pump
Free account: the readings and the manual page (page 72). No card needed.See the full E507 answer

What it means

Compressor shut down due to high pressure condition or open high-pressure switch.

Likely causes

  1. CN1 connector or high pressure switch connector not engaged
  2. High pressure switch open (high pressure protection)
  3. Faulty main PBA

Where to start

  1. Check the CN1 connector and the high pressure switch connector are fully engaged.
  2. Measure across both ends of the CN1 connector. Open circuit: the switch has opened, so check the refrigerant cycle and charge.
  3. Not open and the error stays: replace the main PBA.

The full answer, free

  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 72), right under the answer

Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.