Samsung EHS fault 475
Outdoor unit BLDC fan error
Heat pumpFree account: 2 more checks, the readings and the manual page (page 51). No card needed.See the full 475 answer
What it means
Outdoor unit BLDC fan motor error detected.
Likely causes
- Input power voltage or power connection wrong
- Fan motor plug not connected to the outdoor PCB correctly (CN90 / CN91)
- Obstacle around the fan motor or propeller
- Driver inside the fan motor broken
- Faulty inverter PCB
Where to start
- Check the fan plugs are fully home in CN90 (fan 1) and CN91 (fan 2).
- Power off for 1 minute, unplug each fan and measure the fan cable resistances (see component tests). Out of range: replace the fan motor.
- Plug back in and power on, taking care as this is live: check pins 1-3 over 250 V DC, white-black (4-3) 15 V, and yellow-black (5-3) 1 to 6 V while running. Wrong: replace the inverter PCB.
The full answer, free
- 2 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 51), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full 475 fix, readings and manual page. Free.See the full answer
From the Samsung manual for the EHS. Check the model on the data plate before you order parts.
Other Samsung EHS fault codes
- 108Setting address duplicate error
- 121Error of ROOM temperature sensor in indoor unit short/open
- 122Error of Evaporator_in sensor of indoor unit short/open
- 123Error of Evaporator_out sensor of indoor unit short/open
- 162Outdoor UNIT EEPROM error
- 201CONTROL KIT / outdoor UNIT communication error (matching error)
- 202CONTROL KIT / outdoor UNIT communication error
- 203Communication error between indoor / outdoor INV <-> MAIN MICOM
- 221Outdoor temperature sensor error (open/short)
- 231COND_OUT main temperature sensor error (open/short)
- 251Discharge temperature sensor error (open/short)
- 276Compressor top temperature sensor error (open/short)
- 308Suction sensor error (open/short)
- 321EVI inlet sensor error (open/short)
- 322EVI outlet sensor error (open/short)
- 458Outdoor unit fan error
- 462All currency control COMP stop or CT2 low currency
- 463OLP over heat and comp stop
- 464[inverter] DC peak error
- 466[inverter] DC-link voltage under/over error
- 467COMP revolute error
- 507Comp down due to high pressure or high pressure switch open
- 554GasLeak error
- 590[inverter] data flash error