Samsung EHS fault E123
EVA-OUT temperature sensor error (short/open)
Heat pumpFree account: 3 more checks, the readings and the manual page (page 56). No card needed.See the full E123 answer
What it means
Evaporator outlet temperature sensor circuit detected as short or open
Likely causes
- Short or leakage of the corresponding sensor
- Temperature sensor disconnected from PCB connector
- Temperature sensor failure (resistance out of range)
- Sensor open circuit
- Sensor short circuit
- Wiring fault
Where to start
- Check if temperature sensor is disconnected from the connector in PCB
- If disconnected, restart the system after connecting to the PCB connector; if not disconnected, remove the temperature sensor connector from the PCB and measure the resistance between two terminals
- Compare measured resistance to the temperature/resistance table for 103 Type sensor
The full answer, free
- 3 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 56), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full E123 fix, readings and manual page. Free.See the full answer
From the Samsung manual for the EHS. Check the model on the data plate before you order parts.
Other Samsung EHS fault codes
- 108Setting address duplicate error
- 121Error of ROOM temperature sensor in indoor unit short/open
- 122Error of Evaporator_in sensor of indoor unit short/open
- 123Error of Evaporator_out sensor of indoor unit short/open
- 162Outdoor UNIT EEPROM error
- 201CONTROL KIT / outdoor UNIT communication error (matching error)
- 202CONTROL KIT / outdoor UNIT communication error
- 203Communication error between indoor / outdoor INV <-> MAIN MICOM
- 221Outdoor temperature sensor error (open/short)
- 231COND_OUT main temperature sensor error (open/short)
- 251Discharge temperature sensor error (open/short)
- 276Compressor top temperature sensor error (open/short)
- 308Suction sensor error (open/short)
- 321EVI inlet sensor error (open/short)
- 322EVI outlet sensor error (open/short)
- 458Outdoor unit fan error
- 462All currency control COMP stop or CT2 low currency
- 463OLP over heat and comp stop
- 464[inverter] DC peak error
- 466[inverter] DC-link voltage under/over error
- 467COMP revolute error
- 475Outdoor unit BLDC fan error
- 507Comp down due to high pressure or high pressure switch open
- 554GasLeak error