Samsung EHS fault 902

Water outlet sensor error (open/short)

Heat pump
Free account: 10 more checks, the readings and the manual page (page 51). No card needed.See the full 902 answer

What it means

Water outlet sensor detected as open or short circuit, error source outdoor unit.

Likely causes

  1. Short or leakage of the corresponding sensor
  2. Temperature sensor disconnected from PCB connector
  3. Temperature sensor failure (resistance out of range)
  4. Sensor open or short circuit
  5. Wiring fault
  6. Sensor connector not connected or mismatched by color
  7. Sensor wire broken or poor contact
  8. Temperature sensor fractured or damaged
  9. Resistance value out of range for sensed temperature

Where to start

  1. Check if temperature sensor is disconnected from the connector in PCB
  2. If disconnected, restart the system after connecting to the PCB connector; if not disconnected, remove the temperature sensor connector from the PCB and measure the resistance between two terminals
  3. Compare measured resistance to the temperature/resistance table for 103 Type sensor

The full answer, free

  • 10 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 51), right under the answer

Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

Full 902 fix, readings and manual page. Free.See the full answer

From the Samsung manual for the EHS. Check the model on the data plate before you order parts.