Midea M-Thermal Arctic HT R290 Mono fault P5
The big temperature difference between outlet water temp. and inlet water temp
Heat pumpWhat it means
P5 triggers when the temperature difference between outlet water temperature (Twout) and inlet water temperature (Twin) exceeds specified thresholds. Triggering conditions: Twout-Twin≥30°C in heating/DHW mode; Twout-Twin≥17°C in cooling mode.
Likely causes
- E8/E0 error occurring at roughly the same time (water flow related issue)
- Water flow smaller than normal due to blocked pipe or filter, or incorrect water pressure/flow rate
- Flow switch leak due to faulty sealing ring
- External pump starts before internal pump (PUMPI) starts
- The water flow in the pipe is not consistent with arrow on the flow switch
- Flow switch FS plug (CN8) is not connected properly
- Water flow switch rake mechanically damaged
- Flow switch not installed properly
- Water flow switch mechanically damaged (rake does not trigger contact closure)
- Pump stalling due to impeller obstruction
- Water pump internal failure despite correct wiring
- Water pump malfunction indicated by abnormal indicator light status
- Water pump leak due to faulty sealing ring
- Water pump connection is correct, the water pump icon on the User Interface is lit, while no indicator lights on water pump is lit
- Pump idling
- Pump idling due to insufficient water/air in circuit
Where to start
- Check 'Unit Status-Operation Parameter-water flow' value against normal range
- Pull out Tw_out/Tw_in sensor from plate heat exchanger, leave in air for 10 mins, compare sensor and air temperature
- Check whether heat pump runs in DHW mode and heat exchanger coil size
The full answer, free
- 27 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 140), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error
- H6DC fan motor protection
- H7Compressor voltage protection
- H8H-SEN high pressure sensor error
- H9Tw2 zone 2 water flow temperature sensor error