Midea M-Thermal Arctic HT R290 Mono fault P5

The big temperature difference between outlet water temp. and inlet water temp

Heat pump

What it means

P5 triggers when the temperature difference between outlet water temperature (Twout) and inlet water temperature (Twin) exceeds specified thresholds. Triggering conditions: Twout-Twin≥30°C in heating/DHW mode; Twout-Twin≥17°C in cooling mode.

Likely causes

  1. E8/E0 error occurring at roughly the same time (water flow related issue)
  2. Water flow smaller than normal due to blocked pipe or filter, or incorrect water pressure/flow rate
  3. Flow switch leak due to faulty sealing ring
  4. External pump starts before internal pump (PUMPI) starts
  5. The water flow in the pipe is not consistent with arrow on the flow switch
  6. Flow switch FS plug (CN8) is not connected properly
  7. Water flow switch rake mechanically damaged
  8. Flow switch not installed properly
  9. Water flow switch mechanically damaged (rake does not trigger contact closure)
  10. Pump stalling due to impeller obstruction
  11. Water pump internal failure despite correct wiring
  12. Water pump malfunction indicated by abnormal indicator light status
  13. Water pump leak due to faulty sealing ring
  14. Water pump connection is correct, the water pump icon on the User Interface is lit, while no indicator lights on water pump is lit
  15. Pump idling
  16. Pump idling due to insufficient water/air in circuit

Where to start

  1. Check 'Unit Status-Operation Parameter-water flow' value against normal range
  2. Pull out Tw_out/Tw_in sensor from plate heat exchanger, leave in air for 10 mins, compare sensor and air temperature
  3. Check whether heat pump runs in DHW mode and heat exchanger coil size

The full answer, free

  • 27 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 140), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.

Other Midea M-Thermal Arctic HT R290 Mono fault codes