Midea M-Thermal Arctic HT R290 Mono fault BA

T4 sensor out of operation range protection

Heat pump

What it means

T4 sensor detected temperature outside of normal operation range. In heating/DHW mode, the error occurs when T4≥65℃ or T4<-25℃. In cooling mode, the error occurs when T4≥65℃ or T4<-5℃.

Likely causes

  1. T4 sensor reading out of range
  2. T4 sensor fault
  3. Low ambient temperature (T4<3°C) combined with low water-side temperature triggers freeze protection
  4. Water side temperature dropping below critical thresholds due to low flow, low ambient temperature, or system stoppage
  5. Pump stalling due to impeller obstruction
  6. Feedback signal cable CN17 not connected properly

Where to start

  1. Check T4 (ambient temperature) reading against 3°C threshold
  2. Check Min(Twout,Twin,T1) against 4°C threshold sustained for 5 seconds
  3. Check Min(Twout,Twin,T1) against 2°C threshold (immediate trigger)

The full answer, free

  • 19 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 135), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.