Midea M-Thermal Arctic HT R290 Mono fault EB
Tsolar solar panel temperature sensor error
Heat pumpWhat it means
Tsolar Solar panel temperature sensor error. Occurs when Solar function is on and Solar control is on (User Interface- For Serviceman - Other heat source - Solar function=1 & Solar control=1), while Main Control PCB cannot detect the right Tsolar sensor value.
Likely causes
- Temperature sensor connection on Main Control PCB is loose, misconnected, broken or moisturized
- Main Control PCB fault
- Sensor wiring/connection fault at CN18
Where to start
- If Yes, check if temperature sensor connection on Main Control PCB is loose, misconnected, broken or moisturized; if Yes, reconnect the temperature sensor correctly and keep it dry
- If No to all above, replace Main Control PCB
- Check sensor connection at CN18 on Main Control PCB
The full answer, free
- How to put it right, step by step
- The manual page for this fault (page 111), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E3T1 electric heater/AHS water outlet temperature sensor error
- E4T5 water tank temperature sensor error
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E7Tbt balance tank temperature sensor/final outlet water temperature of cascade system...
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error
- H6DC fan motor protection