Midea M-Thermal Arctic HT R290 Mono fault HD
Communication fault between master unit and slave unit
Heat pumpWhat it means
Communication fault between master unit and slave unit. Triggered when, for a cascade system, the communication failure between master unit and slave unit lasts 2 minutes and above.
Likely causes
- Communication cables between port H1H2E1 disconnected or misconnected
- Dip switch S3-1/2/3 incorrectly set or duplicated address across units
- Time difference of providing power supply for master unit and slave unit is greater than 1 min
- Faulty Main Control PCB
Where to start
- Check communication cables between port H1H2E1 for disconnection or miswiring
- Confirm Dip switch S3-1/2/3 of each unit are all correct and not repeated
- Check time difference of providing power supply between master unit and slave unit
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 106), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the M-Thermal Arctic HT R290 Mono. Check the model on the data plate before you order parts.
Other Midea M-Thermal Arctic HT R290 Mono fault codes
- BAT4 sensor out of operation range protection
- C2IBH (internal backup heater) related fault
- C7Over-high temperature protection for IPM module
- D0Oil return operation active
- E0Water flow failure
- E1Phase loss or phase reversal
- E5T3 outdoor unit heat exchanger bottom temperature sensor error
- E6T4 ambient temperature sensor error
- E8Water flow protection
- E9Th return-air temperature sensor error
- EALow discharge temperature protection
- ECT5_2 water tank temperature sensor error (reserved)
- F1Protection for DC bus undervoltage
- F75Protection for insufficient discharge overheating degree
- FC1TL outdoor unit heat exchanger outlet temperature sensor error
- H1Communication error between main control PCB and inverter PCB
- H2T2 plate heat exchanger outlet refrigerant temperature sensor error
- H3T2B plate heat exchanger inlet refrigerant temperature sensor error
- H4Repeated L1* protection (3 times in 60 mins)
- H5Ta room temperature sensor error
- H6DC fan motor protection
- H7Compressor voltage protection
- H8H-SEN high pressure sensor error
- H9Tw2 zone 2 water flow temperature sensor error