Viessmann Vitodens 100-W fault 468

Burner in a fault state, ionisation current too high during calibration

Gas boiler

What it means

Burner fault state caused by ionisation current measured too high during calibration, often linked to electrode gap or contamination from dust in ventilation air.

Likely causes

  1. Incorrect gap between ionisation electrode and burner gauze assembly
  2. High dust levels in ventilation air (e.g. from construction work)
  3. Deposits on electrodes from foreign bodies in ventilation air (laundry detergents, cleaning agents, toiletries, flue deposits)

Where to start

  1. Check gap between ionisation electrode and burner gauze assembly
  2. Check whether there is a lot of dust in the ventilation air
  3. Check the installation room and flue system for causes of deposits

The full answer, free

  • 11 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 85), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

From the Viessmann manual for the Vitodens 100-W. Check the model on the data plate before you order parts.