Vaillant aroTHERM fault F.731
High-pressure switch open
Heat pumpWhat it means
Refrigerant pressure too high; the integrated high-pressure switch in the outdoor unit has tripped at 41.5 bar (g) or 42.5 bar (abs).
Likely causes
- Refrigerant pressure too high
- Insufficient energy output via the condenser
- Purging the building circuit
- Too low a volume flow as a result of closing single room controls in an underfloor heating system
- Refrigerant flow rate too low (e.g. electronic expansion valve defective, 4-port diverter valve is mechanically blocked, filter is blocked)
- Air in building circuit
- Dirt filter blocked
- Fan unit dirty (cooling mode)
Where to start
- Check that the dirt filter that is in place is permeable
- Cooling mode: Check the fan unit for dirt
- Check the high-pressure switch and high-pressure sensor
The full answer, free
- 9 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 35), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Vaillant manual for the aroTHERM. Check the model on the data plate before you order parts.
Other Vaillant aroTHERM fault codes
- F.073Sensor fault: building circ. water pressure
- F.094Fault: vortex
- F.103Fault: spare part ident
- F.1117Compressor: phase failure
- F.22Heating installation filling pressure critically low
- F.514Sensor fault: compr. inlet temp
- F.517Sensor fault: compr. outlet temp
- F.519Sensor fault: building circuit return temp
- F.520Sensor fault: building circuit flow temp
- F.526Sensor fault: EEV outlet temp
- F.582Fault: EEV
- F.585Sensor fault: capac. outlet temp
- F.723Building circuit: pressure too low
- F.729Compressor outlet temperature too low
- F.732Compressor outlet temperature too high
- F.733Evaporation temperature too low
- F.734Condensation temperature too low
- F.735Evaporation temperature too high
- F.737Condensation temperature too high
- F.741Building circuit: return temp. too low
- F.752Fault: frequency converter
- F.755Fault: 4-port valve position not correct
- F.774Sensor fault: air inlet temp
- F.788Building circuit: pump fault