Ideal Logic System IE Gen 2 fault L02
Ignition lockout
Gas boilerFree account: 4 more checks, the readings and the manual page (page 31). No card needed.See the full L02 answer
What it means
The boiler has failed to light after 5 ignition attempts and has locked out. It is a lockout (L) code; the ignition lockout flowchart is section 4.3.
Likely causes
- Low gas pressure.
- Gas valve wiring or PCB fault (no 24 Vdc at the gas valve).
- Faulty gas valve.
- Faulty spark generator.
- Faulty electrode.
- Blocked condensate or trap.
Where to start
- Press Restart (E) and watch whether the boiler ignites for a short time then goes out.
- Check the gas pressure at the boiler inlet is more than 18 mbar (test point H, page 31).
- Check there is approx 24 Vdc supply at the gas valve.
The full answer, free
- 4 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 31), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full L02 fix, readings and manual page. Free.See the full answer
From the Ideal manual for the Logic System IE Gen 2. Check the model on the data plate before you order parts.
Other Ideal Logic System IE Gen 2 fault codes
- F02Flame loss
- F04Flow thermistor fault
- F05Return thermistor fault
- F0DLow water flow / low water pressure
- F0TRoom thermostat fault
- F0UFlow/return differential greater than 50°C
- F10Spark generator fault
- F13Pump fault
- F15Pump fault
- F16Gas valve fault
- F17Pump fault
- L01Flow temperature overheat lockout
- L04Flow thermistor fault
- L05Return thermistor fault
- L06False flame lockout (flame on before gas valve on)
- L0CRepeated restart lockout
- L0DIgnition lockout: blocked flue/condensate