Worcester Bosch Greenstar 4000 Combi fault 2980
Locking fault: boiler in super lock-out
Gas boilerFree account: the manual page (page 79). No card needed.See the full 2980 answer
What it means
The boiler is in super lock-out: a possibly safety-critical condition has been detected and 5 locking faults have been reset within 15 minutes. The manual warns of a risk of personal injury if it is not remedied and the whole system checked.
Likely causes
- Potentially safety-critical condition detected.
- 5 locking faults reset within 15 minutes.
Where to start
- Diagnose and remedy the original locking fault before trying to unlock (page 79).
- Check the complete system, including sensors and harnesses (page 79).
The full answer, free
- How to put it right, step by step
- The manual page for this fault (page 79), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full 2980 fix, readings and manual page. Free.See the full answer
From the Worcester Bosch manual for the Greenstar 4000 Combi. Check the model on the data plate before you order parts.
Other Worcester Bosch Greenstar 4000 Combi fault codes
- 1010No communication via EMS BUS connection
- 1021Cylinder charging or hot water temperature sensor faulty
- 1037Outside temperature sensor faulty, heating backup operation active
- 1065System pressure sensor faulty or not connected
- 1068Outside temperature sensor or lambda probe faulty
- 1073Short circuit at flow temperature sensor
- 1074No signal from flow temperature sensor
- 1075Heat exchanger temperature sensor short circuit
- 1076Heat exchanger temperature sensor disconnected
- 2085Internal fault
- 214Fan shut down during safety time
- 224Maximum flue gas thermostat or heat exchanger maximum thermostat activated
- 228Flame signal without flame present
- 233Boiler identification module or device electronics faulty
- 234Gas valve electrical fault
- 238Boiler electronics faulty
- 269Flame monitoring
- 281Pump stuck or running in air
- 2910Fault in flue system
- 2915Boiler electronics system fault (fan keeps running after post-purge)
- 2916Boiler electronics system fault (gas valve detected open during post-purge)
- 2923Boiler electronics system fault (unexpected feedback from modulating gas valve)
- 2927Flame failed during burner operation
- 2948No flame signal with low output