Daikin Altherma fault H3-00

Outdoor unit: malfunction of high pressure switch

Heat pump

What it means

High pressure switch is activated when compressor is off.

Likely causes

  1. High pressure switch confirmed faulty during checking procedure
  2. Faulty refrigerant pressure sensor
  3. Poor water flow through high pressure side plate heat exchanger
  4. Incorrect refrigerant charge

Where to start

  1. Perform a check of the high pressure switch
  2. Check refrigerant pressure sensor
  3. Check high pressure side plate type heat exchanger for good water flow and heat exchange

The full answer, free

  • 10 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 46), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.