Daikin Altherma fault F3-00

Outdoor unit: malfunction of discharge pipe temperature

Heat pump

What it means

Discharge pipe thermistor detects a too high temperature.

Likely causes

  1. Closed stop valve in the refrigerant circuit
  2. Refrigerant overcharge or shortage
  3. Non-condensables and/or humidity in the refrigerant circuit
  4. Clogged refrigerant circuit
  5. Faulty 4-way valve
  6. Faulty expansion valve control
  7. Faulty main PCB
  8. Faulty refrigerant side thermistor(s)
  9. Faulty room thermistor
  10. Deviation of thermistor (higher temperature measured than actual).
  11. Bad contact between sensor and pipe
  12. Deviation of outlet water after backup heater thermistor (lower temperature measured than actual)
  13. Deviation of thermistor (lower temperature measured than actual)
  14. Incorrect refrigerant charge
  15. Faulty suction thermistor
  16. Blockages in refrigerant circuit
  17. Faulty discharge pipe thermistor
  18. Domestic hot water tank thermistor measures a higher temperature than actual (component failure)

Where to start

  1. Check that all stop valves of the refrigerant circuit are open (see 4.2 Refrigerant circuit)
  2. Check if the refrigerant circuit is correctly charged (see 4.2 Refrigerant circuit)
  3. Check for the presence of non-condensables and/or humidity in the refrigerant circuit (see 4.2 Refrigerant circuit)

The full answer, free

  • 22 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 43), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.

Other Daikin Altherma fault codes