Daikin Altherma fault EC-00

Abnormal increase tank temperature

Heat pump

What it means

Domestic hot water tank thermistor measures a too high temperature.

Likely causes

  1. Increased water temperature due to an external heat source
  2. Faulty domestic hot water tank thermistor
  3. Faulty hydro PCB
  4. Faulty room thermistor
  5. Deviation of thermistor (higher temperature measured than actual).
  6. Bad contact between sensor and pipe
  7. Deviation of outlet water after backup heater thermistor (lower temperature measured than actual)
  8. Deviation of thermistor (lower temperature measured than actual)
  9. Incorrect refrigerant charge
  10. Faulty expansion valve control
  11. Faulty suction thermistor
  12. Blockages in refrigerant circuit
  13. Faulty discharge pipe thermistor
  14. Domestic hot water tank thermistor measures a higher temperature than actual (component failure)

Where to start

  1. Check the water circuit for an external heat source (see 4.3 Water circuit)
  2. Perform a check of the domestic hot water tank thermistor (see 3.21 Thermistors)
  3. Perform a check of the hydro PCB (see 3.12 Hydro PCB)

The full answer, free

  • 16 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 43), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.