Daikin Altherma fault E5-00

Outdoor unit: overheat of inverter compressor motor

Heat pump

What it means

Compressor overload is detected.

Likely causes

  1. Closed stop valve in the refrigerant circuit
  2. Faulty discharge pipe thermistor or connector fault
  3. Faulty outdoor unit fan motor
  4. Faulty compressor or miswiring of the compressor power supply cable
  5. Faulty expansion valve
  6. Faulty 4-way valve
  7. Faulty refrigerant pressure sensor
  8. Poor water flow through high pressure side plate heat exchanger
  9. Incorrect refrigerant charge
  10. Bad contact between refrigerant loop and inverter heat sink
  11. Lack of refrigerant
  12. Faulty suction thermistor
  13. Blockages in refrigerant circuit
  14. Worn or damaged compressor dampers causing vibration/noise
  15. Compressor guard timer active
  16. Normal inverter control behavior when target temperature achieved
  17. Water pump software control behaviour based on setting [F-0D]
  18. Special software control activated - water loop temperature is too low causing ONLY the backup heater to operate
  19. Faulty compressor winding
  20. High pressure switch confirmed faulty during checking procedure
  21. Flammable refrigerant remaining dissolved in compressor lubricant
  22. Wrong assembly during repair
  23. Excessive heat applied during brazing near compressor pipes

Where to start

  1. Check that all stop valves of the refrigerant circuit are open
  2. Perform a check of the discharge pipe thermistor
  3. Perform a check of the outdoor unit fan motor

The full answer, free

  • 44 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 37), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.

Other Daikin Altherma fault codes